Permit Type: Commercial Building Permit - None BldgNew
Address: E 651 100TH AVE Anchorage
Location:
Work Description: 4800 sq ft metal bldg / tb **Please refer to 08-4646 for geotech, drainage report, SWPPP**tb
Status: Closed
Project Name: DIOMEDE WAREHOUSE BLDG B
Review Type: Structural
Result: Correction
Result Date: 11/23/2011 10:22:58 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C11-2084

Project Name: Diomede Warehouse Bldg. B

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

10/24/2011 – Approved for Footing/Foundation.

11/23/2011 – Initial review (284924).  Comments issued.

 

GENERAL

This review is code compliance review based on the requirements of the International Building Code (IBC), 2006 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.

 

The following comments must be addressed before a permit may be issued.

 

1. PROFESSIONAL ENGINEERING REQUIRED

Please provide pre-engineered building plans sealed and signed by a Professional Engineer registered in the State of Alaska.

Reference: AMC 23.10.104.7; AS 08.48.221

 

2. BUILDING CALCULATIONS

Please provide design calculations for the superstructure.

Reference: IBC Section 1705.2

 

3. SPECIAL INSPECTION PERSONNEL

Please provide a copy of the special inspection letter or agreement used for the other buildings in this development, or provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4

 