Permit Type: Commercial Building Permit - None BldgAlter
Address: 3101 PENLAND PKWY Anchorage
Location:
Work Description: SAFEWAY PHARMACY TI TO EXPAND EXISTING WAITING AREA, ADD AN ADA RESTROOM AND ADD A CONSULTATION ROOM. (JINNY ROSE DAY)
Status: Closed
Project Name: SAFEWAY #0520
Review Type: Architectural
Result: Correction
Result Date: 10/19/2011 12:18:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C11-2021

Phone: 343-8326                                                                           Date: 10/19/2011

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Safeway #520

Review Number: 284211

 

1) STATUS:   10-19-11 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) A2a                   Plumbing and mechanical plans signed and sealed by an Alaska registered professional mechanical engineer will also be required.

 

4) A2a                   Structural plans will be required for the new exterior stairs, the new exterior door and bracing for the overhead roll down fire doors.

 

5) A2a                   Handrails are required on both sides of the new exterior stairs (IBC 1009.12)

 

6) A2a                   Wall types W-2 and W-4 require slip joints at top of wall. Please clarify.

 

7) A2a                   Where is the location of wall type W-3?

 

8) 6/A4                  The new concrete wall at the landing and stairs is required to be at least 42" to create a guard (IBC 1013.1).

 

9) 12/A6               The consulting room sink has ADA requirements to be 34" maximum above the finished floor to the flood rim of the sink or countertop, whichever is higher. (ICC/ANSI A117.1-606.3) 

 

10) 3D/A4                The required water closet clear space is 60 inches minimum, measured perpendicular from the sidewall with no other fixtures or obstructions within that space (ICC/ANSI A117.1-604.3.1). Please clarify for the benefit of the installing contractor.

 

11) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature.

 

 