Permit Number: X11-1636
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: DEFERRED SUB:  seismic calcs for AC equipment / tb
Status: Closed
Project Name: Change Order of Bldg App C11-1317
Review Type: Structural
Result: Correction
Result Date: 9/15/2011 4:08:55 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C11-1317

Change Order Number: X11-1636

Project Name: Aeropostale Dimond Center

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

09/15/2011 – Initial review (283284).  Comments issued.

 

1. LATERAL BRACING

The plans do not show the diagonal bracing for the suspended air conditioning units FCU-1 and FCU-2.  The calculations note (2) or (4) braces, depending on the seismic demand.  Please clarify if the braces are installed, or provide revised design showing lateral bracing is not required.

Reference: ASCE 7 Section 13.6.5