Building Safety Division
Fire systems Comments
Reviewed by: Mark Warren Permit #: F11-1093
Phone: 267-4992 Date: 8/19/2011
Right Fax; 249-7397
Email: warrenmj@muni.org
Permit Manager: Jinny Day
Phone: 267-4992
Email: DayJR@muni.org
Project: Planet fitness
Review Number: 280412
____________________________________________________________________________________
PERMIT STATUS; Corrections.
1) Provide existing pipe drawings showing existing pipe and head locations going back to the riser.
2) Give hydraulic calculations to verify sufficient water supply.
3) Give detail drawings of height of the ceiling and locations of possible obstructions due to soffits or other architectural features.
The above comments were approved with a new set of drawings and information supplied. 9/20/2001.
All submittals should be sent to the permit manager.
Mark Warren, Systems Plan Review
Anchorage Fire Department, Fire Prevention Division
4700 Elmore Road
Anchorage Alaska 99507
907-267-4992 desk
907-720-2245 cell
warrenmj@muni.org