Permit Type: Commercial Building Permit - None ChangeUse
Address: E 2520 16TH AVE Anchorage
Location:
Work Description: Change of use from B to I-4 / tb
Status: Issued
Project Name: Bldg 1 - 2520 E 16TH
Review Type: Architectural
Result: Approved
Result Date: 8/25/2011 12:19:08 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Crafts, Donald E.                                                  Permit #: C11-1586

Phone: 343-8451                                                                          Date: 8/25/2011

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: 2520 & 2530 E. 16th Ave.

Review Number: 281534

 

1.  Status: Architectural Corrections required.  8/1/11   Status: Full Architectural Approval.  8/25/11

 

2.  The following comments based on the 2006 International Building Code (IBC) and 2006 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IEBC, IBC or any federal, state, or local regulations.

 

3.  Drawing Sheet 1 of 1, Floor Plan,   The plans indicate that this building is a change of use from a B occupancy to an I-4 and R-3 occupancy for 5 or fewer persons.  Although this would be allowable, it would require the building to be fully sprinklered per IBC Sections 903.2.5 and 903.2.7 and the local ammendment.  The plans could indicate that this building is a change of use from a B occupancy to an E occupancy in order to eleviate the sprinkler requirement in accordance with IBC Section 903.2.2 and the local ammendment.  Note that this would also alleviate the need for installing smoke and CO detectors.  8/1/11   Resolved.  The plans now indicate that this building is a change of use from a B occupancy to an E occupancy.  8/25/11

 

 4.  Drawing Sheet 1 of 1, Floor Plan, Verify/show fire extinguisher location(s) per IBC Section 906.1.  8/1/11   Resolved.  The  fire extinguisher location is now shown.  8/25/11