Permit F11-1171 ON HOLD awaiting corrections to the following review comments:
1) Provide "Sequence of Events"
2) Type of wiring ? How's it run ? Who's installing it ?
3) What type of Fire Sprinkler system is installed ?
4) What Edition of NFPA is this being installed to ?
5) Elevator Recall req'd. ? Provided by this FACP ? Details if so ?
6) What's the min. height of your pull stations...should be added to the canned detail ?
Craig Torrey @ torreyce@muni.org / 267- 4992. (Tue. & Th only in Plan Review office)
The above comments are approved with additional information recieved. 9/14/2011, Mark Warren.