Permit Number: F11-1146
Permit Type: Commercial Trade Permit - Alteration Fire
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: (51) fire sprinkler devices
Status: Closed
Project Name: Child Permit for C11-1317
Review Type: Fire System
Result: Approved
Result Date: 8/15/2011 8:33:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Structural Comments

 

Reviewed by: Mark Warren                                             Permit #: f11-1146

Phone: 267-4992                                                                        Date: 8/15/2011

Right Fax: 249-7397

Email: warrenmj@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Providence renovation

Review Number: 27993

 

____________________________________________________________________________________

 

1. PERMIT STATUS: Corrections required.

1) Provide information as to the enclosure for display if it is casework or a small room enclosure. If it is a removable piece of casework coverage is not required.

2) It appears that the ceiling will have multiple different heights. Provide an architectural plan section showing possible obstruction due to change of height. 

Note: A responce came back from the designer that indicated there is no glass enclosure at the displays and just shelving below so the adjacent sprinkler head should give coverage. 

It was also indicated that the ceiling is the same level throughout.

Approved 8/18/2011.

 

 

All submittals should be sent to the permit manager.

 

Mark Warren, Systems Plan Review

Anchorage Fire Department, Fire Prevention Division