Permit Number: C11-1586
Permit Type: Commercial Building Permit - None ChangeUse
Address: E 2520 16TH AVE Anchorage
Location:
Work Description: Change of use from B to I-4 / tb
Status: Issued
Project Name: Bldg 1 - 2520 E 16TH
Review Type: Fire
Result: Correction
Result Date: 7/27/2011 4:14:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1.  A change of use requires sprinklers for both an "I" & "R" occupancy per IFC 903.2.5 & 903.2.7 respectively.  Is it your intent to classify the building as an "E" occuppancy and not sprinkler per the local amendment.  If so change the occupancy classification of the building in the code study or provide sprinklers.

2.  Provide a fire extinguisher as required per IFC 906.  Show size, type, & location on plans.

3.  A smoke and carbon monoxide detector is required if the building is classified as R3.