1. Provide a fire extinguisher as required per IFC 906. Show size, type, & location on plans.
2. Nonsprinklered "E" occupancies require a direct exit from each room per 308.5.2 exception. The plans show a divider creating two rooms.
3. What is the age of the occupants as daycare use is calculated @ 35sf per person not 20?
4. Since two exits are required exit signs and emergency light fixtures are also required. Show locations on plans.
5. Is it your intnet to provide a "Knox" keybox per IFC 506. If so a single keybox can serve both buildings. Show location on plans. If requesting a waiver due to the size of the building submit a request in writing waiving the requirement and liability if the fire department requires emergency entry for the file.