Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C11-1317
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location: Ste 110
Work Description: Comm T/I for Suite 110; includes elec, plbg, mech, & struc; (20) inspections / tb
Status: Closed
Project Name: AEROPOSTALE
Review Type: Mechanical
Result: Approved
Result Date: 7/14/2011 8:43:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

1) STATUS:  6-6-11 Comments to be addressed.                    7-14-11 APPROVED.

 

2) The following comments based on the 2006 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.          RESOLVED 7-14-11. 

 

3) Provide structural, seismic and wind load calculations as applicable plus fastening details for FC-1 & 2 and CU-1 & 2 to include engineers stamp and signature, for structural review on a deferred submittal basis.                      RESOLVED 7-14-11.

 

4) M2.01              Please clarify the ventilation air required per IMC 403.          RESOLVED PER RESUBMITTAL RECEIVED 7-14-11.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical plans to include clouded changes, engineers stamp and signature.           RESOLVED 7-14-11.

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter