Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C11-1483
Permit Type: Commercial Building Permit - None BldgNew
Address: 8475 HARTZELL RD Anchorage
Location:
Work Description: 6,700 sq ft VB / tb
Status: Closed
Project Name: ALASKA USA FEDERAL CREDIT UNION
Review Type: Plumbing
Result: Correction
Result Date: 7/22/2011 4:32:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                            Permit #: C11-1483

Phone: 343-8326                                                                          Date: 7/22/2011

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: ALASKA USA FCU

Review Number: 279215

 

1) STATUS:   7-22-11 Comments to be addressed.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) M2.2                 Four sets of the main building roof drains and overflow drains combine to a horizontal 3" main. At 6700 sq ft, and .6" per hour of rainfall for the Anchorage area this will only work for a slope of 1/4" per foot or more (UPC Table 11-2). Please clarify.

 

4) M7.1                 The 1" gas branches serving each boiler (500 MBH @ 20 feet) appear to be under sized per Table 12-8.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS