Exiting Approved 7/18/2011 per FM gray as meeting intent of code. _______________________________________
Disapproved @ counter 6/29/2011 Furch
1. Two exits are required from the suite as travel distance to either exit exceeds the 100ft allowable common path. Since two exits are required the separation shall be 1/3 the diagonal. Exits are approximately 28 ft apart. The diagonal is > 100ft.
2. Since two exits are required exit signs are also required. An additiobnal directional exit sign may be required at the angled hallway as the new signs would not be visible when traveling to the new exit from the reception area of the suite.