1) STATUS: 7-11-11 Comments to be addressed.
2) The following comments based upon the 2006 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) M300 The 1-1/4" gas supply to GUH-2 thru 5 is shown on M301 as 1". Please clarify.
4) M700 A boiler room floor drain is required (IMC 1004.6) with vented P-trap (UPC 901.0) and trap seal protection (UPC 1007.0).
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.