Permit Number: C11-1407
Permit Type: Commercial Building Permit - None BldgNew
Address: 4140 B ST Anchorage
Location:
Work Description: New construction 11,350 sq ft warehouse & 22,700 sq ft office; 20% deduction for core & shell / tb
Status: Closed
Project Name: B STREET NORTH BLDG
Review Type: Mechanical
Result: Correction
Result Date: 7/25/2011 1:19:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C11-1407

Phone: 343-8326                                                                          Date: 7/25/2011

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: North B Street Building

Review Number: 278119

 

1) STATUS:  7-25-11 Comments to be addressed.

 

2) The following comments based on the 2006 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations as applicable plus fastening details for B-1 thru 3, AHU-1, CH-1, RF-1 & 2, EU-1, CU-1, FOS-1 and the Generator to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) M5.0              The 42" round S/A and the 42" x 42" E/A ducts penetrating the shaft require fire/smoke dampers (IMC716.5.3).

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical plans to include clouded changes, engineers stamp and signature.

 