1) STATUS: 6-9-11 Comments to be addressed.
2) The following comments based upon the 2006 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.
3) T1.0 The list of applicable codes should also include the 2003 ICC/ANSI A117.1 "Accessible and Useable Buildings and Facilities".
4) A1.0 Wall Type 3 requires a slip track at the top of wall to accomodate varying winter snow loads on the roof. Please clarify.
5) 2/A1.1 The horizontal water closet grab bar also has a maximum height of 36" to the top of the gripping surface. (ICC/ANSI A117.1-609.4)
6) 2/A1.1 A vertical side wall grab bar is also required. (ICC/ANSI A117.1-604.5.1)
7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature.