Permit Number: C11-1185
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location: SUITE C18B FIRST FLOOR
Work Description: T/I: ELEC/PLUMB/MECH (8) *TINA*
Status: Closed
Project Name: GNC LIVE WELL
Review Type: Fire
Result: Correction
Result Date: 5/25/2011 11:25:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1.  Since the occupant load is > 50 two exits are required.   Doors 3 & 4 swing against the direction of travel.

2.  A separate submital, review, & permit is required for additions and changes to the existing fire alarm system.  this submital nay be deferred.

3.  Verify and provide additional emergency light fixtures as required to meet the minimum 1 ft candle.  Per the drawings there is only one em light in the retail area near door 2.  there are none shown at door 6.  Show all EM fixtures whether existing or new in order to evaluate entire area.