1. Status: Architectural Corrections required. 5/19/11
2. The following comments based on the 2006 International Building Code (IBC) and 2006 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IEBC, IBC or any federal, state, or local regulations.
3. Drawing CS-1, (IBC Building) Code Information, Verify information in the Code study that provides the type of construction for the existing building is IIB as indicated. I believe that the type of construction for the existing 5th Avenue Mall building is IA or IB. 5/19/11
4. Drawing CS-1, (IBC Building) Code Information, Verify information in the Code study that provides the occupancy load calculations for the GNC space as indicated. I believe that the occupancy load in the sales (customer) area of more than 50 will require a second code compliant exit. The existing exit in the back of the store may be used for this purpose; however, it would require a clear path of egress through the storage space with exit signs and egress lighting. 5/19/11