2/3/2014 Permit canceled per Charles Starr / tb

Status: Closed
Project Name: ALASKA REGIONAL MOB B
Review Type: Electrical
Result: Approved
Result Date: 3/25/2011 11:26:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

5/20/2011

The engineer has prrovided clarificaiton on this small job at Alaska Regional. Approved

 

5/2/2011

We are waiting the engineer to provide us with the information listed below. Correction Required

 

REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
Sheet E208a is designed by a registered professional electrical engineer of the State of Alaska. The design shall include existing service load calculations, panel schedules with connected and NEC demand loads, wiring method, and one-line diagram. Please note that the patient care areas must comply with NEC section 517.13. Please indicate if any of the loads connected to the emergency generator system.