Accessibility upgrades to toilet rooms and other misc elements-gjs
2/3/2014 Permit canceled per Charles Starr / tb
5/20/2011
The engineer has prrovided clarificaiton on this small job at Alaska Regional. Approved
5/2/2011
We are waiting the engineer to provide us with the information listed below. Correction Required
REQUIREMENT OF ELECTRICAL SCOPE OF WORK:Sheet E208a is designed by a registered professional electrical engineer of the State of Alaska. The design shall include existing service load calculations, panel schedules with connected and NEC demand loads, wiring method, and one-line diagram. Please note that the patient care areas must comply with NEC section 517.13. Please indicate if any of the loads connected to the emergency generator system.