Permit Number: C11-1055
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2751 DEBARR RD Anchorage
Location:
Work Description:

Accessibility upgrades to toilet rooms and other misc elements-gjs

2/3/2014 Permit canceled per Charles Starr / tb

Status: Closed
Project Name: ALASKA REGIONAL MOB B
Review Type: Architectural
Result: Correction
Result Date: 4/7/2011 11:32:45 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

1) STATUS:   4-7-11 Comments to be addressed.

 

2) The following comments based upon the 2006 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) 0191/A2.08a               Specify the compliant side for the flush valve on the existing urinal as mentioned in note #J5.

 

4) 2,3,9 & 15/A401                    The height of the horizontal grab bar is a maximum of 36" to the top of the gripping surface (not centerline) per ICC/ANSI A117.1-609.4.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature.

 