Permit Number: X11-1025
Permit Type: Commercial Building Permit - ChangeOrdr ChangeUse
Address: E 300 DIMOND BLVD Anchorage
Location:
Work Description: DESIGN CALCS
Status: Closed
Project Name: Change Order of Bldg App CB111126
Review Type: Structural
Result: Correction
Result Date: 4/11/2011 2:36:22 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT STATUS

04/11/2011 – X11-1025 - Initial review (272035).  Comments issued.

5/18/2011 - Anchorage of MUA approved. Water heater has not been approved.

 

CONSTRUCTION REQUIRING SPECIAL INSPECTION

Please clarify the attachment method for the water heater.  The structural design notes two methods: lag screw and post-installed masonry anchors.  Please note that masonry anchors are subject to special inspection requirements of IBC Chapter 17.

Reference:  AMC 23.10.104.8.1; ICC-ES ESR-1385 Section 4.3

 

The following is required if post-installed masonry anchors are used:

 

SPECIAL INSPECTION PERSONNEL

Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4