Permit Number: 10 5130
Permit Type: Commercial Building Permit - None BldgNew
Address: 4951 BUSINESS PARK BLVD Anchorage
Location: 4951 BUSINESS PARK BLVD 00922134000
Work Description: Work Descr: 41,004 sq ft (B), 1090 sq ft (S), 1010 sq ft (A3), Remarks: JRD
Status: Closed
Project Name: ANCHORAGE NEIGHBORHOOD CLINIC
Review Type: Architectural
Result: Correction
Result Date: 3/22/2011 4:06:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1.  Status: Architectural Corrections required.  3/21/11

 

2.  The following comments based on the 2006 International Building Code (IBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. G002, Code Summary;  Add the following to the Accessory Occupancy requirement per IBC Section 508.3.1: and shall not exceed the tabular values in Table 503, without height and area increases in accordance with Sections 504 and 506 for such Accessory Occupancies.  3/21/11

 

4.  Drawing No. G002, Code Summary;  Details 01, 02,  & 03, First, Second, and Third Level Floor Code Plans, at the north stairwell (Stair 1), show a 1 hour fire resistive wall in the exterior section of wall for the exit stairwell or show a 1 hour fire resistive wall in the portion of the building that is at an angle of less than 180 degrees to the exit stairwell for a distance of at least 10 feet per IBC Sec. 1020.1.4.  3/21/11

  

5.  Drawing No. A601, Door Schedule;  Please provide door hardware details on the Door Schedule that meet the requirements of IBC Section 1008.1.8 and 1008.1.9.  Specifically, pacic/exit hardware on the exit stairwell doors, conference room doors, and other exit doors.  Verify the interior vestibule doors are in compliance as well.  3/21/11

  

6.  Drawing No. A602, Door Schedule and Types;  All glass doors require safety glazing per IBC section 2406.3.  Verify that safety glazing is provided in all required locations (including windows, when required) per IBC section 2406.3.  3/21/11

 

7.  Drawing No. A202, Exterior Elevations and Drawing No. A202, Exterior Elevations; Some of the wall types for the exterior walls includes panel which appears to contain foam plastic.  A thermal barrier is required per IBC Section 2603.5 for the exterior wall (foam plastic) or show compliance to the requirements in IBC Section 2603.5.1 thru 2603.5.7 or show compliance to the requirements in IBC Section 2603.9.  Please provide exterior wall cut sheets and details to include the thermal barrier or clarify code compliance.  3/21/11

 

8.  Drawing No. A103, Third Level Floor Plan; There are two shower rooms (Men’s and Woman’s) located on the third floor of this building.   Verify accessibility for both shower rooms (including grab Bars) per "Accessible and Useable Buildings and Facilities" (ICC/ANSI A117.1) 2003, section 608.  3/21/11

 

9.  Drawing No. A103, Third Level Floor Plan; There is a lavatory in the break room located on the third floor of this building.   Verify accessibility for the lavatory per "Accessible and Useable Buildings and Facilities" (ICC/ANSI A117.1) 2003, section 606.  3/21/11