Permit Number: CB111058
Permit Type: Commercial Building Permit - None BldgAlter
Address: 9138 ARLON ST Anchorage
Location: STE A1
Work Description: 1600 SQ FT TENANT IMPROVEMENT (JINNY ROSE DAY)
Status: Issued
Project Name: ALASKA RIGHT TO SLEEP
Review Type: Electrical
Result: Approved
Result Date: 2/28/2011 4:33:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: David Abuobaid                                                   Permit #: CB11-1058

Phone: 343-8333                                                                        Date: 2/28/2011

Fax:      249-7775

Email: AbuobaidDH@muni.org

Permit Manager: JINNY Rose Day

Phone: 343-8338

Email: dayjr@muni.org

Project: Alaska Right to Sleep (Fax: 907-274-4445)

____________________________________________________________________________________

5/23/2011

The electrical plan have been revised to reflect the field report by Mike Green.

 

1.   Please address the following comments for full approval. 2/28/2011

 

2.  The following comments based on the 2008 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

 

3.  EQUIPMENT REQUIRES THIRD PARTY LISTING:
Please be aware that all equipment will require and be checked for third party listing per NEC 110-3. Any new or existing equipment to be reused or relocated will be checked for listing by the electrical inspector. Any equipment found without a listing will be required to go through testing to gain approval. Inspector to field verify. NO RESPONSE REQUIRED.

 

4.  PARKING LIGHT POLE (GROUND MOVEMENT):

There are no engineering details to account for the ground movement. NEC Section 300.5(J) requires that where direct buried conductors, raceway, or cables are subject to movement by settlement or frost, direct buried conductors, raceways, or cable shall be arranged to prevent damage to the enclosed conductors or to equipment connected to the raceways. The arrangement we require is that metal rigid conduit, 5 feet minimum be installed between the base of the pole and underground conduits. Please address.

 

5.  EXISTING SERVICE LOAD CALCULATIONS:

Sheet E-3 (Existing Service Entrance Load Calculations). The plans have no calculations for the feeder loads for the existing section of the building as required by NEC Section 220.87. Please add the power factor and state how you obtain the existing load. Please address.

 

PANEL SCHEDULE; NEC CONNECTED AND DEMAND LOADS:

Sheet E-3 (Panel Schedule - Connected and NEC Demand Loads). The electrical design has panel schedule with every circuit breaker as space. No load in the panel schedule P1. Panel schedule shall be provided with connected loads and the NEC demand loads. Refer to the Anchorage Administrative Code AAC 23.10.302.3. Please address.
       

7.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.