Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: CB111081
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Tenant improvement- remodel of existing mall space
Status: Closed
Project Name: GNC Live Well
Review Type: Architectural
Result: Approved
Result Date: 2/9/2011 5:02:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1) STATUS: 2-1-11 Comments to be addressed.                     2-8-11 APPROVED.

2) The following comments based on the 2006 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.                         RESOLVED 2-8-11.

3) E/A-5 & G/A-5            The horizontal ADA water closet grab bars are required to be 33" up to 36" AFF to the top of the gripping surface.                    RESOLVED PER RESUBMITTAL RECEIVED 2-8-11.

4) J/A-5                The term non-combustible plywood was used in the construction of the bathroom ceiling assembly. It is assumed that the term fire retardent treated plywood was intended which is still considered combustible construction. Plywood is not permitted for this application in Type II construction (IBC 603). Please address.                       RESOLVED PER RESUBMITTAL RECEIVED 2-8-11.

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.                     RESOLVED 2-8-11.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter