Permit Number: 97 5559
Permit Type: Commercial Building Permit - None BldgAlter
Address: 700 G ST Anchorage
Location:
Work Description: Work Descr: canopy entrance, add on- 128 sq ft, Remarks:
Status: Expired
Project Name:
Review Type: Architectural
Result: Approved
Result Date: 9/8/1997 2:22:40 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Eave overhangs and similar architectural projections must comply with UBC Section 705. Projections from walls of Type II construction shall be of noncombustible materials. Therefore, wood must not be used in this canopy. Please eliminate the wood. Please verify compliance of the skylight glazing and framing with UBC Section 2409.5. Please include snow drift effects per UBC Section 1641. All elements of the structural frame of Type II-FR buildings must be a two-hour fire-resistive assembly, while roof assemblies must be one-hour assemblies (UBC Table 6-A). Please verify compliance. Please verify compliance of roof drain system with MOA Handout No. 3 Please verify compliance of the plastic foam insulation with UBC Section 2602