Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: 10 5066
Permit Type: Commercial Building Permit - None BldgAlter
Address: 4901 SPENARD RD Anchorage
Location:
Work Description: Work Descr: T/I LOBBY RENOVATION (6) INSPECTIONS, Remarks: TINA
Status: Closed
Project Name: COURTYARD BY MARRIOTT
Review Type: Structural
Result: Correction
Result Date: 1/18/2011 12:20:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT STATUS

01/14/2011 – Initial review (252675).  Comments issued.

01/18/2011 - Reviewed responses (257051).  Special inspector information required for approval.

 

GENERAL

This review is code compliance review based on the requirements of the International Building Code (IBC), 2006 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.

 

The following comments must be addressed before a permit may be issued.

 

STATEMENT OF SPECIAL INSPECTIONS

Please provide a detailed statement of special inspections in accordance with IBC Chapter 17. This may be provided on the plans or as a separate document.

Reference: IBC Section 1705.2

1/18/11 - Resolved.  Statement provided on Sheet S-101.  MMP

 

SPECIAL INSPECTION PERSONNEL

Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4

1/18/11 - Not resolved.  No information provided this review.  MMP

 

CHORD ANCHORAGE AT UPPER SHEAR WALL

Refer to Sheet S102, Calculations Pg. 8 thru 13.  The calculations show the tension loads from the upper shear wall holdown need to be distributed among multiple anchors.  Please clarify the analysis, as the anchors directly in line with the strap will take all of the load initially due to the stiffness.

Reference:  IBC Section 1604.4

1/18/11 - Resolved.  Revised anchorage analysis provided.  MMP

 

RESISTING MASS AT FOUNDATION
Refer to Sheet S102.  It is unclear whether there is sufficient dead load mass at the foundation to resist the uplift due to the upper story shear walls.  Please clarify.

Reference:  IBC Section 1604.8

1/18/11 - Resolved.  Revised footing mass provided.  MMP

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS