Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
06 5311
Permit Type:
Commercial Building Permit - None BldgNew
Address:
1717 TIDEWATER RD Anchorage
Location:
Work Description:
Work Descr: New shipping kiosk system, Remarks: tb
Status:
Issued
Project Name:
HORIZON LINES NEW SHIPPING KIO
Review Type:
Public Engineering
Result:
Approved
Result Date:
5/31/2006 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
C(1): Please provide storm drain depth of bury, percent grade, and invert information for the proposed 12" diameter SD. Insulation or a thaw wire may be required, per DCM 2.070. {Manhole will replace existing hole and exposed culvert. 5-31-6, MG}
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501