Permit Number: 06 5269
Permit Type: Commercial Building Permit - None BldgNew
Address: 3645 AIRCRAFT DR Anchorage
Location: changed from 3635 Aircraft 6/3/14, K.Wilson
Work Description:

Work Descr: 6000 sq ft**NPDES PAID UNDER PERMIT 06-5266**TB, Remarks: tb  **12/6/2011 transferred elec to 06-5266**tb

8/19/2013 OK to reactivate permit per S. Walsh / tb

Status: Closed
Project Name: AIRCRAFT DRIVE HANGAR #2
Review Type: Public Engineering
Result: Approved
Result Date: 6/28/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

C(1): Please revise detail 3.1 on sheet C8.1 to show a minimum of 28 inches of Type II/IIA base fill course fill per the page 7 Geotechnical Report recommendation and include a geotextile separation to minimize fine infiltration into the base fill course per DCM 1.070.G (Log B-2 41% fines & wet, B-5 14% fines & static water table). Satisfied per revised pavement plan and geotechnical recommendation.