Permit Number: 06 5266
Permit Type: Commercial Building Permit - None BldgNew
Address: 3635 AIRCRAFT DR Anchorage
Location: address was changed from 4737 Lakeshore Dr; 5-14-12, K.Wilson
Work Description: Work Descr: 7200 sq ft, Remarks: tb **11/24/09 Keep file active**tb**2/18/10 new owner; contractor transfer to owner**tb
Status: Closed
Project Name: AIRCRAFT DRIVE HANGARS #1
Review Type: Public Engineering
Result: Approved
Result Date: 6/28/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

C(1): Please revise detail 3.1 on sheet C8.1 to show a minimum of 28 inches of Type II/IIA base fill course fill per the page 7 Geotechnical Report recommendation and include a geotextile separation to minimize fine infiltration into the base fill course per DCM 1.070.G. (Log B-2 41% fines & wet, B-5 14% fines & static water table). Satisfied per revised pavement plan and geotechnical recommendation.