Permit Number: 10 5130
Permit Type: Commercial Building Permit - None BldgNew
Address: 4951 BUSINESS PARK BLVD Anchorage
Location: 4951 BUSINESS PARK BLVD 00922134000
Work Description: Work Descr: 41,004 sq ft (B), 1090 sq ft (S), 1010 sq ft (A3), Remarks: JRD
Status: Closed
Project Name: ANCHORAGE NEIGHBORHOOD CLINIC
Review Type: Right of Way
Result: Correction
Result Date: 12/29/2010 11:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

  1. Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit.
  2. Show, callout, dimension, and label all easements on the Plot Plan.
  3. Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field.
  4. Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements.
  5. Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments.
C(1): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(2): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(3): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(4): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(5): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(1): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(2): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(3): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(4): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(5): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(1): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(2): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(3): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(4): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(5): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(1): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(2): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(3): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(4): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(5): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(1): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(2): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(3): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(4): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(5): Provide pavement cut replacement and trench details that match MASS or just refer to MASS unless having the correct details on the field drawings will benefit the construction contractor in the field. C(1): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(2): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(3): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(4): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(5): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(1): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(2): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(3): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(4): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(5): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(1): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(2): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(3): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(4): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(5): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(1): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(2): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(3): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(4): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(5): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(1): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(2): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(3): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(4): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(5): Show all easements on all the civil plan views so the reviewers may determine the construction impacts on the intent and use the use of the easements. C(1): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(2): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(3): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(4): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(5): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(1): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(2): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(3): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(4): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(5): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(1): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(2): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(3): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(4): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(5): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(1): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(2): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(3): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(4): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(5): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(1): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(2): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(3): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(4): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(5): Right of Way Permit required for the two new entry drives and any other work in the rights of way or certain easments. C(1): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(2): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(3): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(4): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(5): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(1): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(2): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(3): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(4): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(5): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(1): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(2): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(3): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(4): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(5): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(1): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(2): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(3): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(4): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(5): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(1): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(2): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(3): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(4): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(5): Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, including but not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit. C(1): Show, callout, dimension, and label all easements on the Plot Plan. C(2): Show, callout, dimension, and label all easements on the Plot Plan. C(3): Show, callout, dimension, and label all easements on the Plot Plan. C(4): Show, callout, dimension, and label all easements on the Plot Plan. C(5): Show, callout, dimension, and label all easements on the Plot Plan. C(1): Show, callout, dimension, and label all easements on the Plot Plan. C(2): Show, callout, dimension, and label all easements on the Plot Plan. C(3): Show, callout, dimension, and label all easements on the Plot Plan. C(4): Show, callout, dimension, and label all easements on the Plot Plan. C(5): Show, callout, dimension, and label all easements on the Plot Plan. C(1): Show, callout, dimension, and label all easements on the Plot Plan. C(2): Show, callout, dimension, and label all easements on the Plot Plan. C(3): Show, callout, dimension, and label all easements on the Plot Plan. C(4): Show, callout, dimension, and label all easements on the Plot Plan. C(5): Show, callout, dimension, and label all easements on the Plot Plan. C(1): Show, callout, dimension, and label all easements on the Plot Plan. C(2): Show, callout, dimension, and label all easements on the Plot Plan. C(3): Show, callout, dimension, and label all easements on the Plot Plan. C(4): Show, callout, dimension, and label all easements on the Plot Plan. C(5): Show, callout, dimension, and label all easements on the Plot Plan. C(1): Show, callout, dimension, and label all easements on the Plot Plan. C(2): Show, callout, dimension, and label all easements on the Plot Plan. C(3): Show, callout, dimension, and label all easements on the Plot Plan. C(4): Show, callout, dimension, and label all easements on the Plot Plan. C(5): Show, callout, dimension, and label all easements on the Plot Plan.