Project Name: NORTHERN HOLDINGS
Review Type: Fire System
Result: Approved
Result Date: 9/13/2010 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Install correct temperature heads as per NFPA 409. C(2): Unclear as to what the uncovered shaft is at 3 and G. C(3): Show position of the FDC and Bell on the civil drawing to verify access and approach visibility. C(4): Verify that the general contractor is aware that the pump room is to be one hour rated. C(5): No alarm permit application is in place, verify who will be doing the alarm and tie in to the riser for monitoring.