Permit Number:
08 5043
Permit Type:
Commercial Building Permit - None BldgAdd
Address:
2801 DEBARR RD Anchorage
Location:
Work Description:
Work Descr: 2,689 sq ft add'n & T/I, Remarks: tb
Status:
Issued
Project Name:
ALASKA REGIONAL LAB & PHARMACY
Review Type:
Fire System
Result:
Approved
Result Date:
8/31/2009 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. Provide hydraulic calculations for the plans (area were mech room 127 is had 8 sprinkler heads now has 15 sprinkler heads. Show were new and relocated heads are on the plans sprinkler head to the south of Microm office 108 is 8 feet off the wall sprinkler head in blood bank by existing storage is 8 feet of the wall can not verify if this a small room plans and submittals incomplete Work completed in phase 1 before permit is approved - working without an approved permit fees apply