Permit Number: 08 5043
Permit Type: Commercial Building Permit - None BldgAdd
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: Work Descr: 2,689 sq ft add'n & T/I, Remarks: tb
Status: Issued
Project Name: ALASKA REGIONAL LAB & PHARMACY
Review Type: Fire System
Result: Approved
Result Date: 6/8/2009 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): room 127 add notification to mechanical room C(2): Room 127 add pull station to exit C(3): Room 125 does not have complete strobe coverage C(4): Room 119 does not have complete strobe coverage C(5): Add pull station at stairs of Vestibule 1-100A C(6): Add pull station to room 113 at exit C(7): No Strobe coverage in room 112 - add C(8): Improper strobe coverage in room 107 add or correct coverage C(9): no strobe coverage in room 106/104 - add C(10): Improper strobe in room 103 - need to correct C(11): Pull station in cooridor east of room 101 is not within 5 feet of and exit - relocate C(12): What are the rooms in the cooridor to the east of room 101 C(13): No strobe coverage in cooridor east of room 101 provide as required by NFPA 72 C(14): fire alarm device layout does not comply with the 2006 IFC 907 and 2007 NFPA 72 make corrections as required and resubmit plans