Permit Number: 10 4846
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 601 5TH AVE Anchorage
Location:
Work Description: Work Descr: Roof top installation of cellular antennas & associated equipment; (4) inspections, Remarks: tb
Status: Issued
Project Name: KEY BANK
Review Type: Structural
Result: Approved
Result Date: 10/28/2010 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): PERMIT STATUS (no response required) 10/18/2010: Review completed, comments issued. C(2): Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2006 International Building Code (IBC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations. C(3): Please clarify what the antenna sleds are. If these are projections above the roof they must be of the same constructiontype as the building. Reference IBC section 1509.2. C(4): Please provide details showing the connection of the antennas to the sleds. Reference AAC section 23.10.104.8. C(5): When sliding of the platform was checked, it appears that 0.9*DL was used. This should be 0.7 to include the effects of the vertical seismic load 0.2*Sds*DL.