Permit Number: 09 5071
Permit Type: Commercial Building Permit - None BldgNew
Address: 2810 O'MALLEY RD Anchorage
Location:
Work Description:

Work Descr: 4284 SQ FT, Remarks: JRD

 

Status: Closed
Project Name: GREEK ORTHODOX CHURCH
Review Type: Traffic Engineering
Result: Approved
Result Date: 4/20/2010 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(8): New church required parking should provide ADA accessible spaces near the accessible entrance equal to the ratio of ADA spaces required for total parking requirement. Include a van access ADA stall near the new church accessible entrance.///////3/15/10 mma. /////////////////Petitioner (Krochina) feels that ADA layout as shown will work for the site. If it does not they will make adjustments. mma 4/20/10 C(9): ADA accessible car aisles must be a minimum 5ft wide. ADA van accessible aisles must be a minimum 8ft wide.