Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
09 5071
Permit Type:
Commercial Building Permit - None BldgNew
Address:
2810 O'MALLEY RD Anchorage
Location:
Work Description:
Work Descr: 4284 SQ FT, Remarks: JRD
Status:
Closed
Project Name:
GREEK ORTHODOX CHURCH
Review Type:
Plumbing
Result:
Approved
Result Date:
5/11/2010 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(9): 2-25-10 NEW The first floor drinking fountain is missing from the plumbing plans and a mop sink is missingfrom both levels and the plumbing fixture schedule. RESOLVED PER E-MAIL RECEIVED 5-10-10.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501