Permit Number:
09 5071
Permit Type:
Commercial Building Permit - None BldgNew
Address:
2810 O'MALLEY RD Anchorage
Location:
Work Description:
Work Descr: 4284 SQ FT, Remarks: JRD
Status:
Closed
Project Name:
GREEK ORTHODOX CHURCH
Review Type:
Mechanical
Result:
Approved
Result Date:
5/11/2010 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(5): 2-25-10 NEW 2/M4.1 WE ARE NOT AWARE THAT THERE ARE ANY HORIZONTAL FIRE DAMPERS LISTED FOR USE IN WOOD FRAMED FLOORING. PROVIDE SUBMITTAL LITERATURE OF SUCH A LISTED FIRE DAMPER OR USE A RATED SHAFT WITH FIRE/SMOKE DAMPERS AT ALL PENETRATIONS. RESOLVED PER E-MAIL RECEIVED 5-10-10.