Permit Number:
09 5019
Permit Type:
Commercial Building Permit - None BldgNew
Address:
6000 SOUTH AIRPARK PL Anchorage
Location:
Work Description:
Work Descr: 2745 sq ft VB **6/18/10 144 sq ft S2 & 151 sq ft U for Observation Tower per CO#3**tb, Remarks: tb
Status:
Issued
Project Name:
FBI CLASSROOM AND RANGE FACILI
Review Type:
Mechanical
Result:
Approved
Result Date:
5/11/2010 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(10): The double doors #102A and #102B to storage room #102 are required to be rated for 45 Minutes and may not be undercut. RESOLVED PER RESUBMITTAL RECEIVED 4-30-10. C(11): When the Enclosed Firing Area #103 is not being used, please clarify the path used to relieve the air pressure created by FC-2. (IMC 403.1) RESOLVED PER RESUBMITTAL RECEIVED 4-30-10. C(12): The sniper tower has a compressor located within the structure and the building appears to have no heat. When temperatures drop below freezing, the compressor operation would be questionable. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 4-30-10.