Permit Number: 09 5019
Permit Type: Commercial Building Permit - None BldgNew
Address: 6000 SOUTH AIRPARK PL Anchorage
Location:
Work Description: Work Descr: 2745 sq ft VB **6/18/10 144 sq ft S2 & 151 sq ft U for Observation Tower per CO#3**tb, Remarks: tb
Status: Issued
Project Name: FBI CLASSROOM AND RANGE FACILI
Review Type: Fire
Result: Approved
Result Date: 6/24/2010 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(12): SPECIFICATIONS FOR FIRE APPARATUS ACCESS ROADS: SURFACE REQUIRED TO SUPPORT 80000 LBS. PLEASE ADDRESS. IFC 503.2. 4/21/10. RESOLVED. Road currently supports Airport Fire Trucks. 5/5/10 Venta C(13): FIRE LANE NO PARKIING SIGNS: IFC APP D 103.6 AND D103.6.1 - REQUIRES FIRE LANE SIGN NO PARKING SIGNS SHALL BE POSTED EVERY 100 FT. ON BOTH SIDES FOR 20-25 FT WIDE FIRE ACCESS ROADS. 4/21/10. RESOLVED. WILL POST AS REQ'D. 5/5/10 Venta C(14): FIRE APPARATUS ACCESS ROAD GATES: GATES SECURING APPARATUS ACCESS ROADS SHALL COMPLY WITH ALL OF THE CRITERIA IN IFC APP D103.5 INCLUDING: MINIMUM SIZE 20 FT WIDE; KNOX PADLOCKS FOR FIRE DEPT ACCESS; MANUAL OPERATION BY ONE PERSON IF REQUIRED; SWINGING OR SLIDING TYPE. 4/21/10. RESOLVED. Gates meet code req'mts. 5/5/10 Venta C(15): AMMUNITION STORAGE: Is ammunition stored on premises? Please advise storage location. Ammunition storage required tomeet code requirements IFC 105.6.14; 3301; 3304. 4/21/10. Please advise where ammunition will be stored on the premises as shooting range is unable to operate w/o ammunition. 5/5/10 Venta NOT RESOLVED. PLEASE ADDRESS. 5/19/10 Venta RESOLVED6/24/2010 Furch - No ammo storage on site. C(16): OCCUPANT LOAD: Every room or space that is an assembly occupancy shall have a permanent occupant load sign posted in a conspicuous place near the main exit or exit access doorway from the room or space. MAXIMUM OCCUPANT LOAD. Classrooms 101 and 102 require signage. Please address. IBC 1004.3. RESOLVED. Will post classrooms. 5/5/10 Venta C(17): SNIPER PLATFORM: Please advisethe use of this area? Show square footage, exiting detail on plans. Is this area included in building occupant load? Please address. 4/21/10. RESOLVED. Sniper platform added to Code study and building occupant load. 5/5/10 Venta
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS