Permit Type: Commercial Building Permit - None BldgNew
Address: E 651 100TH AVE Anchorage
Location:
Work Description: Work Descr: 4800 sq ft **OK for contractor to p/u elec permit per Mary Jane w/ Fuchs Electric**, Remarks: mgm
Status: Closed
Project Name: DIOMEDE WAREHOUSE D
Review Type: Mechanical
Result: Approved
Result Date: 7/31/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Provide structural and seismic calculations plus fastening details for MAU-1 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 7-31-08. C(2): STATUS: 6-25-08 Comments to be addressed. 7-31-08 APPROVED. C(3): The following comments based on the 2006 International Building, Mechanical and Fuel Gas Codes must be resolvedbefore a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 7-31-08. C(4): M2.1 The East wall is on the property line and is required to be a 2-Hour fire wall. Per IMC 501.2.1 exhaust ducts may not discharge at the property line and per IBC 705.11, ducts may not penetrate a fire wall. RESOLVED PER RESUBMITTAL RECEIVED 7-28-08.