Permit Number: 08 4647
Permit Type: Commercial Building Permit - None BldgNew
Address: E 651 100TH AVE Anchorage
Location:
Work Description: Work Descr: 4800 sq ft **OK for contractor to p/u elec permit per Mary Jane w/ Fuchs Electric**, Remarks: mgm
Status: Closed
Project Name: DIOMEDE WAREHOUSE D
Review Type: Fire
Result: Approved
Result Date: 7/16/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): FIRE REVIEW STATUS: Disapproved 7/01/08 furch 07/15/08 approved furch C(2): EMERGENCY LIGHTING: The 3 lights in the large bay may not provide an adequate light level. The fixtures are separated by over 50 ft. Verify/confirm level is adequate or add additional fixtures in the center of the room. C(3): EXIT SIGNAGE: The code study indicates two exits are required & provided. Exit signs have been provided at the exterior door but the partitionwall does not have signage at door 102. Is it the intent to have access to two required exits? If so, signs are required on each side of door 102 as it is an exit access door. Add as required per IBC 1011.