Permit Number: 07 6110
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 401 6TH AVE Anchorage
Location:
Work Description: Work Descr: lobby renovation, Remarks: mgm // demo permit: 08-4218. -mgm 03/12/08 // Kyco Inc auth xfer of P permit to Alkota P & H -mgm 05/06/08 //
Status: Issued
Project Name: SHERATON ANCHORAGE
Review Type: Fire
Result: Approved
Result Date: 3/28/2008 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): FIRE REVIEW STATUS: DISAPPROVED 2/1/2008 Carpenter Approved Floors 3-14 only Carpenter Below comments still relevant. DISAPPROVED 15 AND 16 FLOORS. 3/18/08 Carpenter See comments 9 and 10 below APPROVAL includes floors 15 and 16. 3/28/08 Carpenter C(2): Any work done to Fire Alarm system such as taking down or replacing horns or horn/strobes shall be by a approved fire alarm person. C(3): FIRE PROTECTION SYSTEMS - Permits: Submit plans and apply for separate review and permits for Sprinkler and Fire Alarm as needed. C(4): Wood Slats on ceilings and walls: A7.02: Verify the wood meets the requirements of IBC 803.4.1 or 803.4.2. C(5): Elevator cab interior change shall be as approved by Chalon Rein. Elevator Inspector. (343-8369) And shall meet the requirements of the Elevator code. RESOLVED- CONTRACTOR TO CONFIRM ANY WORK WITH ELEVATOR DIVISION. C(6): Wood: Verify any wood used on this projects is allowed by IBC Ch 6 for construction type. RESOLVED 3/17/08 C(7): Meeting 206: Provide exit signs. RESOLVED 3/14/08 C(8): L16: Exiting has changed provide additional exit signs. NOT RESOLVED 3/17/08 Not enough exit signs. Not resolved 4/18/08 RESOLVED TO BE PROVIDED PER AMY GREEN 3/28/08 206-623-6368 C(9): Floor Level 15: Existing rated corridor ends at Elevator Lobby. Access to second exit would be by leaving rated corridor and passing through Josephine's. Please address as it is unclear how the exiting system works on this level Not resolved 3/18/08 RESOLVED 3/28/08. EXISTING exiting through Josephines to be maintained. Doors unlocked and exit signs to be in place per Andy Krippner. C(10): FIRE PROTECTION SYSTEMS-REPORTS: Provide a current service report for each fire system in the building. All deficiencies must be corrected prior to calling for a fire final. RESOLVED 3/17/08 Will do.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS