Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
06 6077
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 900 5TH AVE Anchorage
Location:
Work Description:
Work Descr: T/I of existing main lobby, Remarks: tb
Status:
Issued
Project Name:
5TH AVENUE BLDG
Review Type:
Fire
Result:
Approved
Result Date:
10/30/2006 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
C(1): FIRE REVIEW STATUS: Approved 10/30/06 Furch for lobby remodel per plans. Inspector to field verify fire extinguisher, sprinkler, & fire alarm system.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501