Permit Type: Commercial Building Permit - None BldgNew
Address: 3645 AIRCRAFT DR Anchorage
Location: changed from 3635 Aircraft 6/3/14, K.Wilson
Work Description:

Work Descr: 6000 sq ft**NPDES PAID UNDER PERMIT 06-5266**TB, Remarks: tb  **12/6/2011 transferred elec to 06-5266**tb

8/19/2013 OK to reactivate permit per S. Walsh / tb

Status: Closed
Project Name: AIRCRAFT DRIVE HANGAR #2
Review Type: Architectural
Result: Approved
Result Date: 10/4/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): After discussion with Rick Button (contact person) the change order will be revised to show a nonrated wall between the two hangar bays, 7-18-06. See below comments 8-23-06. Approved 10-4-06. C(2): The following comments based on the 2003 IBC must be resolved before the change order will be approved. C(3): Since the west wall is less than 30 feet from the property line, it must be 2 hour rated in accordance with section 412.2.1. The original plansshow a two exterior wall; however the change order now indicates a one hour wall. Please address. Resolved 10-4-06 per revised plans.