Project Name: AIRCRAFT DRIVE HANGAR #2
Review Type: Fire
Result: Approved
Result Date: 6/22/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): FIRE REVIEW STATUS: DISAPPROVED 5/8/06 Carpenter APPROVED 6/22/06 FEC All comments addressed. C(2): WATERFLOW: Provide information on flow available. Show hydrant locations & distances from property and building. AWWU computer projections may be accepted for permitting.1500 GPM REQUIRED. 2460 GPM OK hYDRANTS LOCATIONS OK 6/17/06 C(3): KEY BOX: Must install adjacent to the front main entrance at 6' above grade prior to the CO inspection. Knox box info may be obtained at Fire Prev 4700 S Bragaw, 267-4900. C(4): ADDRESS: Provide a street address for the building. The address shall be plainly visible/legible from the street or road fronting the building. Each Hangar shall be identified individually. This as #2. C(5): GAS METER protection: Provide bollards: minimum 4" diameter by six feet (3' buried in a 15" diameter concrete footing; 3' above ground) and they must be filled with concrete. C(6): FIRE ACCESS: Provide a 20' wide lane to within 150' of all portions of the building. Use a minimum clear height of 13'6" and a 40' inside diameter turn radius. Show access on the plans. Show intended fire access on plans. resolved 6/17/06 FEC C(7): FIRE PROTECTION SYSTEMS - Permits: Submit plans and apply for separate review and permits for SPRINKLER SYSTEM. C(8): SPRINKLER SYSTEM: (A) Shall be monitored offsite at 24 hour approved location. (B) Sprinkler main control valves location shall be identified with sign on door of room containing it.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS