Permit Number: 06 5266
Permit Type: Commercial Building Permit - None BldgNew
Address: 3635 AIRCRAFT DR Anchorage
Location: address was changed from 4737 Lakeshore Dr; 5-14-12, K.Wilson
Work Description: Work Descr: 7200 sq ft, Remarks: tb **11/24/09 Keep file active**tb**2/18/10 new owner; contractor transfer to owner**tb
Status: Closed
Project Name: AIRCRAFT DRIVE HANGARS #1
Review Type: Fire
Result: Approved
Result Date: 10/6/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): CO#1 Approved @ counter 10/06/06 Furch (DISAPPROVED 9/11/06 Furch - C(2): Please clarify & revise submittal as IBC 412.2.2 requires exterior walls located less than 30 feet from a property line, lot lines or a public way shall have a fire resistiverating not less tha 2 hours. Submittal stamped August 18, 2006 referrs to 1 hr walls.