Permit Number: 05 6349
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1602 HILLCREST DR Anchorage
Location:
Work Description: Work Descr: STANDBY GENERATOR INSTALLATION, Remarks: PJB
Status: Issued
Project Name: WEST HIGH SCHOOL
Review Type: Electrical
Result: Approved
Result Date: 4/20/2006 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments are based on the 2002 National Electrical Code and should be resolved before a permit is issued. This correction list is not a building permit.The approval of plans and specifications does not permit the violation of any section of the NEC, or any federal, state or local amendments to these codes C(2): Please provide details of emergency generator: generator listing, electrical rating, transfer switches, separation of circuits, fuel supply onsite, load shedding, emergency panel schedules, and feeder schedule. C(3): ELECTRICAL STATUS: CORRECTIONS REQUIRED C(4): THE GENERATOR IS STANDBY NOT EMERGENCY. ELECTRICAL STATUS: APPROVED AS NOTED