Permit Number:
05 5226
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
Work Descr: installation of art - aircraft on concourse c, Remarks: cs
Status:
Issued
Project Name:
CONCORSE C
Review Type:
Structural
Result:
Approved
Result Date:
6/13/2005 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): Please verify the suspended aircraft can move 12" and 45 degrees off the vertical in any direction without contacting an obstruction. Reference IBC section 1621.2.1 Exception. C(2): Please provide verification of the material the clevis is being attached on on the aircraft. WAB - 4/26/2005