Permit Number:
04 6272
Permit Type:
Commercial Building Permit - None BldgNew
Address:
301 Gull AVE Anchorage
Location:
Work Description:
Work Descr: 8640 sqft fabric structure, Remarks: gjs
Status:
Closed
Project Name:
BLDG #1
Review Type:
Plumbing
Result:
Approved
Result Date:
1/26/2005 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): The following comments based on the 2000 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform plumbing Code or any federal, state or local regulations. RESOLVED PER RESUBMITTAL RECEIVED 1-19-05. C(2): The gas piping system generally appears to be undersized. Also, the total capacity for the meter should be 2400 MBH. Please clarify sizing methods used. RESOLVED PER RESUBMITTAL RECEIVED 1-19-05.