Permit Number: 02 6051
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Work Descr: Installation of EDS/ETD baggage screening equipment with associated electrical and misc work in existing lobby and ato spaces, Remarks: gjs LETTER TO BE SENT OUT
Status: Expired
Project Name: SOUTH TERMINAL
Review Type: Structural
Result: Approved
Result Date: 11/20/2002 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Please provide confirmation of the 60,000-psi yielding strength used in your calculations for the steel reinforcement. C(2): I find that the scanner located at Grid 13, between Grids O & P, is bearing on an existing floor opening and may be inadequately supported. Please address. C(3): Please review the design loads on existing beam "DB-54" - I find the loads to be significantly higher and the beam may be undersized. C(4): Please resubmit plans and calculations as a "change order".