Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
02 5465
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
1076 OCEAN DOCK RD Anchorage
Location:
Work Description:
Work Descr: building pump pit, Remarks: cs **note Storm Water still needs to be paid $300.00 10/02/02.**
Status:
Expired
Project Name:
Review Type:
Electrical
Result:
Approved
Result Date:
12/31/2002 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): ELECTRICAL STATUS (C.O.#3): APPROVED AS NOTED. The revison applied to sheet rack expansion, phase # 3.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501